DHI-300DUCTABLEWASTE OIL HEATERInstallation andOperatingInstructionsLanair Waste Oil Heaters & Boilers4109 Capital CircleJanesville,Wisconsin 5354
Section 2 - Heater InstallationQUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST10TYPICAL INSTALLATION:HEATER/CHIMNEY
Section 2 - Heater InstallationVisit our website at: www.lanair.com11General Requirements1. Do not install the heater on a combustible surface of any
Section 3 - Chimney/Vent SystemQUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST12Figure 2 - Typical Chimney Installat
Section 3 - Chimney/Vent SystemVisit our website at: www.lanair.com13General Requirements (cont.)4. Install a U.L. listed barometric damper in the chi
Section 3 - Chimney/Vent SystemQUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST1417. If you are unable to attain the
Section 4 - DraftVisit our website at: www.lanair.com15Figure 3The Lanair heater should have a (negative) -.02 draft reading when cold, and a (negativ
Section 5 - Fuel Supply Tank InstallationQUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST16General Requirements1. The
Section 6 - Fuel Supply Pump/PipingVisit our website at: www.lanair.com17General Requirements1. Mount the fuel supply pump in a horizontal position (s
Section 6 - Fuel Supply Pump/PipingQUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST1814. Install the fuel supply line
Section 7 - Air Supply InstallationVisit our website at: www.lanair.com19General Requirements1. Install an air pressure supply line connection to the
BEFORE YOU BEGIN INSTALLATION...IMPORTANTRead and understand this manual completely before beginning installation.• This heater is for commercial and
Section 8 - Electrical ConnectionsQUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST20CAUTION: HAZARD OF ELECTRICAL SHO
Visit our website at: www.lanair.com21Section 8 - Electrical ConnectionsFigure 7Section 13 - Service / MaintenanceQUESTIONS?... Contact Customer Servi
Section 8 - Electrical ConnectionsQUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST22Fuel Supply Pump Electrical Insta
Section 9 - ControlsVisit our website at: www.lanair.com23• Room Thermostat:The room thermostat automatically controls the on/off operation of the hea
Section 9 - ControlsQUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST24• Electric Air Solenoid ValveThe Electric Air S
Section 10 - Priming The Fuel PumpVisit our website at: www.lanair.com25Priming The Fuel Pump1. The fuel level in the supply tank must beabove the che
Section 10 - Priming The Fuel PumpQUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST2612. Turn the room thermostat belo
Section 10 - Priming The Fuel PumpQUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST2612. Turn the room thermostat belo
Section 10 - Priming The Fuel PumpVisit our website at: www.lanair.com25Priming The Fuel Pump1. The fuel level in the supply tank must beabove the che
Section 9 - ControlsQUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST24• Electric Air Solenoid ValveThe Electric Air S
DHI-300 DUCTABLE WASTE OIL HEATERInstallationand OperatingInstructionsTableofContents:Rules For Safe Installation and Operation . . . . . . . . . . ..
Section 9 - ControlsVisit our website at: www.lanair.com23• Room Thermostat:The room thermostat automatically controls the on/off operation of the hea
Section 8 - Electrical ConnectionsQUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST22Fuel Supply Pump Electrical Insta
Visit our website at: www.lanair.com21Section 8 - Electrical ConnectionsFigure 7Section 13 - Service / MaintenanceQUESTIONS?... Contact Customer Servi
Section 8 - Electrical ConnectionsQUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST20CAUTION: HAZARD OF ELECTRICAL SHO
Section 7 - Air Supply InstallationVisit our website at: www.lanair.com19General Requirements1. Install an air pressure supply line connection to the
Section 6 - Fuel Supply Pump/PipingQUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST1814. Install the fuel supply line
Section 6 - Fuel Supply Pump/PipingVisit our website at: www.lanair.com17General Requirements1. Mount the fuel supply pump in a horizontal position (s
Section 5 - Fuel Supply Tank InstallationQUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST16General Requirements1. The
Section 4 - DraftVisit our website at: www.lanair.com15Figure 3The Lanair heater should have a (negative) -.02 draft reading when cold, and a (negativ
Section 3 - Chimney/Vent SystemQUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST1417. If you are unable to attain the
Section 1 - General Specifications & HazardsQUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST4No. Description1 Mou
Section 3 - Chimney/Vent SystemVisit our website at: www.lanair.com13General Requirements (cont.)4. Install a U.L. listed barometric damper in the chi
Section 3 - Chimney/Vent SystemQUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST12Figure 2 - Typical Chimney Installat
Section 2 - Heater InstallationVisit our website at: www.lanair.com11General Requirements1. Do not install the heater on a combustible surface of any
Section 2 - Heater InstallationQUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST10TYPICAL INSTALLATION:HEATER/CHIMNEY
Section 1 - General Specifications & HazardsVisit our website at: www.lanair.com9• The Lanair Heater provides the owner with a dependable, versati
Section 1 - General Specifications & HazardsQUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST8OPTIONAL J-PUMPNo. D
Section 1 - General Specifications & HazardsVisit our website at: www.lanair.com7Section 14 - TroubleshootingQUESTIONS?... Contact Customer Servic
Section 1 - General Specifications & HazardsQUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST6DHI-300 FRONTSection
Section 1 - General Specifications & HazardsVisit our website at: www.lanair.com513222485679No. Description1 8" Chimney Exhaust2 Mounting Hol
Section 1 - General Specifications & HazardsQUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST4No. Description1 Mou
Section 1 - General Specifications & HazardsVisit our website at: www.lanair.com513222485679No. Description1 8" Chimney Exhaust2 Mounting Hol
DHI-300 DUCTABLE WASTE OIL HEATERInstallationand OperatingInstructionsTableofContents:Rules For Safe Installation and Operation . . . . . . . . . . ..
BEFORE YOU BEGIN INSTALLATION...IMPORTANTRead and understand this manual completely before beginning installation.• This heater is for commercial and
DHI-300DUCTABLEWASTE OIL HEATERInstallation andOperatingInstructionsLanair Waste Oil Heaters & Boilers4109 Capital CircleJanesville,Wisconsin 5354
Section 1 - General Specifications & HazardsQUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST6DHI-300 FRONTSection
Section 1 - General Specifications & HazardsVisit our website at: www.lanair.com7Section 14 - TroubleshootingQUESTIONS?... Contact Customer Servic
Section 1 - General Specifications & HazardsQUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST8OPTIONAL J-PUMPNo. D
Section 1 - General Specifications & HazardsVisit our website at: www.lanair.com9• The Lanair Heater provides the owner with a dependable, versati